This technical article describes a comparative study that was undertaken by Intermarine, with the assistance of EnginSoft, between using the Flownex simulation environment and Intermarine’s manual or classic methods
This technical article describes a comparative study that was undertaken by Intermarine, with the assistance of EnginSoft, between using the Flownex simulation environment and Intermarine’s manual or classic methods (both of which were compared with actual field data from on-board measurements) to predict pressure losses in the various piping systems that convey fluids on board a vessel.
The fluids conveyed by the piping systems on vessels must reach each of their users at the right pressure and flow conditions. Various accessories in these piping systems, such as valves, bends, fittings and pipes, induce pressure losses. These pressure losses need to be predicted to select or verify the size of pump required for the piping system to prevent a number of potential problems. The objective of the study was to test the accuracy and reliability of the results obtained using Flownex, the time taken to execute the analyses, the applicability of Flownex to the shipbuilding environment’s requirements.
There are various piping systems that convey many different fluids on board a vessel. Each fluid must reach its user at the right pressure and flow conditions. Accessories such as valves, bends, fittings and pipes induce pressure losses (as a result of factors such as pressure (p), flow rate (q) and pipe size (diameter, A)). The designer has to calculate these probable pressure losses in the pipeline in order to select (or verify) the size of the pump to be installed in the piping system to prevent a number of possible problems. Usually, these calculations to predict pressure losses are performed “manually” using the procedures described in the technical literature, such as the method of equivalent lengths, with the help of software such as Microsoft Excel or similar, and with the lengths and the fittings information being derived from one-line diagram (2D CAD software).
The Shipyard wanted to test the capability of the 1-D computational fluid dynamics (CFD) software known as Flownex Simulation Environment (SE), provided by EnginSoft S.p.A., as a pipeline solver for its naval piping systems. The results obtained with Flownex were compared with the “manual / classic” method described above
The testing activity focused on the "auxiliary seawater cooling system", in which we concentrated on different lines such as the suction and delivery lines of the pumps, and the inlet and outlet lines of the diesel generator. The Flownex model was designed with the following characteristics:
Some special fittings, such as expansion joints that had no similar components already available in the Flownex library, were replaced with “basic pipe” elements of equivalent length that corresponded to their concentrated losses.
The pipelines were calculated at two different flow rates: the lower at approximately 39 m3/h, corresponding to the operating point of the pump (for improved efficiency under design conditions), and the higher at approximately 112 m3/h, corresponding to the flow rate when all the users are running the cooling system simultaneously (the worst potential condition, furthest from the design conditions).Lower flow rate case (39 m3/h)
Notes:
The Flownex results showed a slight increase in pressure loss values (1) indicating a more conservative behavior in the software with respect to the “manual” calculation. The same behavior is shown in (2), except for the Outlet line, because of the orifice device installed (these elements require further investigation, beyond the scope of this article).
Notes:
In this case (112 m3/h), interesting also due to the availability of field data measured on the suction line, it can be noted that both calculations (Excel with 0,671 bar, Flownex with 0,684 bar of pressure drop) have a conservative behavior related to the pressure gauge measurements (0,397 bar), thus predicting a higher pressure loss than the ones measured directly on board. No actual data is available for the delivery line, so we could only compare the “manual” calculations with the Flownex ones. The first returned a pressure drop of 0,546 bar, the second reported a pressure drop of 0,602 bar. In addition,, in this case, the tested software displayed more conservative behavior.
Fig. 2 - Suction and delivery lines of the pump (39 m3/h)
Fig. 3 - Inlet and outlet lines of the diesel generator
In summary, the study led to the following conclusions:
For more information please contact: Erik Mazzoleni - EnginSoft | e.mazzoleni@enginsoft.com
CASE STUDY
This technical paper presents an analysis process to accurately examine the environmental loads and structural stability of a Floating photovoltaic (PV) power plant. The method includes a hydrodynamic analysis of the Floating PV in its water-based environment as well as a structural analysis of its structural stability based on the characteristics of motion it undergoes.
ansys energy